ACQ550-U1 User’s Manual 79
Parameters
4108 0% VALUE Unit and scale defined by par. 4106 and 
4107
-0.0
4109 100% 
VALUE Unit and scale defined by par. 4106 and 
4107
- 100.0
4110
SET POINT SEL 0…2, 8…17, 19…20 1 1 (AI1) 
4111 INTERNAL SETPNT Unit and scale defined by par. 4106 and 
4107
-40.0
4112
SETPOINT MIN -500.0…500.0% 0.1% 0.0%
4113
SETPOINT MAX -500.0…500.0% 0.1% 100.0%
4114
FBK SEL 1…13 1 1 (ACT1)
4115 FBK MULTIPLIER 0.000 = NOT SEL, -32.768…32.767 0.001 0.000 (NOT SEL)
4116
ACT1 INPUT 1…7 1 2 (AI2) 
4117
ACT2 INPUT 1…7 1 2 (AI2) 
4118
ACT1 MINIMUM -1000…1000% 1% 0%
4119
ACT1 MAXIMUM -1000…1000% 1% 100%
4120
ACT2 MINIMUM -1000…1000% 1% 0%
4121 ACT2 MAXIMUM -1000…1000% 1% 100%
4122
SLEEP SELECTION -6…7 1 0 (NOT SEL)
4123
PID SLEEP LEVEL 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm 0.0 Hz / 0 rpm
4124 PID SLEEP DELAY 0.0…3600.0 s 0.1 s 60.0 s
4125
WAKE-UP DEV Unit and scale defined by par. 4106 and 
4107
-0.0
4126
WAKE-UP DELAY 0.00…60.00 s 0.01 s 0.50 s
Group 42: EXT / TRIM PID
4201 GAIN 0.1…100.0 0.1 1.0
4202
INTEGRATION TIME 0.0 = NOT SEL, 0.1…3600.0 s 0.1 s 60.0 s
4203
DERIVATION TIME 0.0…10.0 s 0.1 s 0.0 s
4204 PID DERIV FILTER 0.0…10.0 s 0.1 s 1.0 s
4205
ERROR VALUE INV 0 = NO, 1 = YES 10 (NO) 
4206
UNITS 0…127 1 4 (%)
4207 UNIT SCALE 0…4 1 1
4208 0% 
VALUE Unit and scale defined by par. 4206 and 
4207
-0.0
4209 100% 
VALUE Unit and scale defined by par. 4206 and 
4207
- 100.0
4210
SET POINT SEL 0…2, 8…17, 19…20 1 1 (AI1) 
4211
INTERNAL SETPNT Unit and scale defined by par. 4206 and 
4207
-40.0
4212
SETPOINT MIN -500.0…500.0% 0.1% 0.0%
4213
SETPOINT MAX -500.0…500.0% 0.1% 100.0%
4214
FBK SEL 1…13 1 1 (ACT1)
4215
FBK MULTIPLIER 0.000 = NOT SEL, -32.768…32.767 0.001 0.000 (NOT SEL)
4216
ACT1 INPUT 1…7 1 2 (AI2) 
4217
ACT2 INPUT 1…7 1 2 (AI2) 
4218
ACT1 MINIMUM -1000…1000% 1% 0%
4219
ACT1 MAXIMUM -1000…1000% 1% 100%
4220
ACT2 MINIMUM -1000…1000% 1% 0%
Code Name Range Resolution Default User S