236 ACQ550-U1 User’s Manual
Fieldbus adapter
PID Control setpoint source
Using the following settings to select the fieldbus as the setpoint source for PID
loops:
Communication fault
When using fieldbus control, specify the drive’s action if serial communication is lost.
Feedback from the drive – FBA
Inputs to the controller (drive outputs) have pre-defined meanings established by the
protocol. This feedback does not require drive configuration. The following table lists
a sample of feedback data. For a complete listing, see all parameters listed in
section Complete parameter descriptions on page 83.
Scaling
To scale the drive parameter values see the following sections, as appropriate:
Actual Value scaling on page 247 (ABB Drives profile technical data)
Actual Value scaling on page 249 (Generic profile technical data).
Drive parameter Value Setting
Protocol
reference
4010 SET POINT SEL (Set 1) 8 (COMM VALUE 1)
9 (COMM+AI1)
10 (
COMM
*
AI1)
Setpoint is input reference 2
(+/-/
*
AI1)
4110
SET POINT SEL (Set 2)
4210 SET POINT SEL (Ext/Trim)
Drive parameter Value Description
3018
COMM FAULT FUNC 0 (NOT SEL)
1 (
FAULT)
2 (
CONST SP7)
3 (LAST SPEED)
Set for appropriate drive
response.
3019 COMM FAULT TIME Set time delay before acting on a communication loss.
Drive parameter Protocol reference
0102
SPEED
0103 OUTPUT FREQ
0104 CURRENT
0105 TORQUE
0106 POWER
0107 DC BUS VOLTAGE
0109 OUTPUT VOLTAGE
0301 FB CMD WORD 1 – bit 0 (STOP)
0301 FB CMD WORD 1 – bit 2 (REV)
0118
DI 1-3 STATUS – bit 0 (DI3)