90 ACQ550-U1 User’s Manual
Parameters
0305 FAULT WORD 1
Read-only copy of the Fault Word 1.
When a fault is active, the
corresponding bit for the active fault is
set in the Fault Words.
Each fault has a dedicated bit
allocated within Fault Words.
See section Fault listing on page 252
for a description of the faults.
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0306 FAULT WORD 2
Read-only copy of the Fault Word 2.
See parameter 0305.
0307 FAULT WORD 3
Read-only copy of the Fault Word 3.
See parameter 0305.
0308 ALARM WORD 1
When an alarm is active, the
corresponding bit for the active alarm
is set in the Alarm Words.
Each alarm has a dedicated bit
allocated within Alarm Words.
Bits remain set until the whole alarm
word is reset. (Reset by writing zero to
the word.)
The control panel displays the word in
hex. For example, all zeros and a 1 in
Bit 0 displays as 0001. All zeros and a
1 in Bit 15 displays as 8000.
0309 ALARM WORD 2
See parameter 0308.
Code Description
Bit # 0305, FAULT WORD 1 0306, FAULT WORD 2 0307, FAULT WORD 3
0 OVERCURRENT Obsolete EFB 1
1 DC OVERVOLT THERM FAIL EFB 2
2 DEV OVERTEMP OPEX LINK EFB 3
3 SHORT CIRC OPEX PWR INCOMPATIBLE SW
4 Reserved CURR MEAS
USER LOAD CURVE
5 DC UNDERVOLT SUPPLY PHASE Reserved
6 AI1 LOSS ENCODER ERR Reserved
7 AI2 LOSS OVERSPEED Reserved
8 MOT OVERTEMP Reserved Reserved
9 PANEL LOSS DRIVE ID Reserved
10 ID RUN FAIL CONFIG FILE System error
11 MOTOR STALL SERIAL 1 ERR System error
12 CB OVERTEMP EFB CON FILE System error
13 EXT FAULT 1 FORCE TRIP System error
14 EXT FAULT 2 MOTOR PHASE System error
15 EARTH FAULT OUTP WIRING Param. setting fault
Bit # 0308, ALARM WORD 1 0309, ALARM WORD 2
0 OVERCURRENT Reserved
1 OVERVOLTAGE PID SLEEP
2 UNDERVOLTAGE ID RUN
3 DIR LOCK Reserved
4 IO COMM START ENABLE 1 MISSING
5 AI1 LOSS START ENABLE 2 MISSING
6 AI2 LOSS EMERGENCY STOP
7 PANEL LOSS ENCODER ERROR
8 DEVICE OVERTEMP FIRST START
9 MOTOR TEMP Reserved
10 Reserved USER LOAD CURVE
11 MOTOR STALL START DELAY
12 AUTORESET Reserved
13 AUTOCHANGE Reserved
14 PFC I LOCK Reserved
15 Reserved Reserved