ACQ550-U1 User’s Manual 69
Parameters
Parameters
Complete parameter list
The following table lists all parameters. Table header abbreviations are:
•S
= Parameters can be modified only when the drive is stopped.
• User = Space to enter desired parameter values.
Some values depend on the “construction” as indicated in the table by
“-U1:” = Setup and parts specific to US installation and NEMA compliance.
Refer to the type designation on the drive, for example ACQ550-U1-08A8-4.
Code Name Range Resolution Default User S
Group 99: START-UP DATA
9901 LANGUAGE 0…16 / 0…3 1 0 (ENGLISH)
9902
APPLIC MACRO -3…7 1 6 (PID CONTROL)
9904
MOTOR CTRL MODE 1 or 2 = VECTOR:SPEED,
3=
SCALAR:FREQ
13 (SCALAR:FREQ)
9905
MOTOR NOM VOLT -U1-yyyy-2: 115…345 V 1 V -U1-yyyy-2: 230 V
-U1-yyyy-4: 230…690 V -U1-yyyy-4: 460 V
-U1-yyyy-6: 288…862 V -U1-yyyy-6: 575 V
9906
MOTOR NOM CURR 0.2 · I
2hd
… 2.0 · I
2hd
0.1 A 1.0 · I
2hd
9907 MOTOR NOM FREQ 10.0…500.0 Hz 0.1 Hz -U1: 60.0 Hz
9908
MOTOR NOM SPEED 50…30000 rpm 1 rpm Size dependent
9909
MOTOR NOM POWER 0.2…3.0 · P
hd
-U1: 0.1 hp 1.0 · P
hd
9910 ID RUN 0 = OFF/IDMAGN, 1 = ON 10 (OFF/IDMAGN)
9915
MOTOR COSPHI 0= IDENTIFIED, 0.01…0.97 0.01 0 (IDENTIFIED)
Group 01: OPERATING DATA
0101 SPEED & DIR -30000…30000 rpm 1 rpm -
0102
SPEED 0…30000 rpm 1 rpm -
0103
OUTPUT FREQ 0.0…500.0 Hz 0.1 Hz -
0104
CURRENT 0.0…2.0 · I
2hd
0.1 A -
0105
TORQUE -200.0…200.0% 0.1% -
0106
POWER -2.0…2.0 · P
hd
0.1 kW -
0107
DC BUS VOLTAGE 0…2.5 · V
dN
1V -
0109
OUTPUT VOLTAGE 0…2.0 · V
dN
1V -
0110
DRIVE TEMP 0.0…150.0 C0.1C-
0111
EXTERNAL REF 1 0.0…500.0 Hz / 0…30000 rpm 0.1 Hz / 1 rpm -
0112
EXTERNAL REF 2 0.0…100.0% (0.0…600.0% for torque) 0.1% -
0113
CTRL LOCATION 0=LOCAL, 1 = EXT1, 2 = EXT21 -
0114
RUN TIME (R) 0…9999 h 1 h -
0115
KWH COUNTER (R) 0…65535 kWh 1 kWh -
0116
APPL BLK OUTPUT 0.0…100.0% (0.0…600.0% for torque) 0.1% -
0118
DI 1-3 STATUS 000…111 (0…7 decimal) 1 -