114 ACQ550-U1 User’s Manual
Parameters
2105 DC HOLD SPEED
Sets the speed for DC Hold. Requires that parameter 2104
DC HOLD CTL = 1 (DC HOLD).
2106 DC CURR REF
Defines the DC current control reference as a percentage of parameter 9906
MOTOR NOM CURR.
2107 DC BRAKE TIME
Defines the DC brake time after modulation has stopped, if parameter 2104 is 2 (
DC BRAKING).
2108 START INHIBIT
Sets the Start inhibit function on or off. If the drive is not actively started and running, the Start inhibit function ignores
a pending start command in any of the following situations and a new start command is required:
A fault is reset.
Run Enable (parameter 1601) activates while start command is active.
Mode changes from local to remote.
Control switches from
EXT1 to EXT2.
Control switches from
EXT2 to EXT1.
0 =
OFF – Disables the Start inhibit function.
1 =
ON – Enables the Start inhibit function.
2109 EMERG STOP SEL
Defines control of the Emergency stop command. When activated:
Emergency stop decelerates the motor using the emergency stop ramp (parameter 2208
EMERG DEC TIME).
Requires an external stop command and removal of the emergency stop command before drive can restart.
0 = NOT SEL – Disables the Emergency stop function through digital inputs.
1 =
DI1 – Defines digital input DI1 as the control for Emergency stop command.
Activating the digital input issues an Emergency stop command.
De-activating the digital input removes the Emergency stop command.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for Emergency stop command.
•See
DI1 above.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as the control for Emergency stop command.
De-activating the digital input issues an Emergency stop command.
Activating the digital input removes the Emergency stop command.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for Emergency stop command.
•See
DI1(INV) above.
2110 TORQ BOOST CURR
Sets the maximum supplied current during torque boost.
See parameter 2101
START FUNCTION.
Code Description