ACQ550-U1 User’s Manual 183
Embedded fieldbus
5309 EFB STATUS This parameter indicates the internal status of the EFB
Protocol as follows:
• IDLE – EFB Protocol is configured but not receiving
messages.
• TIMEOUT – Time between valid messages has
exceeded the interval set by parameter 3019.
• OFFLINE – EFB Protocol is receiving messages NOT
addressed to this drive.
• ONLINE – EFB Protocol is receiving messages
addressed to this drive.
• RESET – EFB Protocol is in reset.
• LISTEN ONLY – EFB Protocol is in listen-only mode.
5310 EFB PAR10 Not used for Comm
setup.
Sets the response turnaround time
in milliseconds in addition to any
fixed delay imposed by the protocol.
When this protocol is selected, the
default value is: 5 ms
5311 EFB PAR11 Not used for Comm
setup.
This parameter, together with
parameter 5317,
EFB PAR 17, sets
BACnet Device Object Instance
IDs:
• For the range 1 to 65,535: This
parameter sets the ID directly
(5317 must be 0). For example,
the following values set the ID to
49134: 5311 = 49134 and 5317 =
0.
• For IDs > 65,335: The ID equals
5311’s value plus 10,000 times
5317’s value. For example, the
following values set the ID to
71234: 5311 = 1234 and 5317 =
7.
5314 EFB PAR14 Not used for Comm setup.
5315 EFB PAR15 Not used for Comm setup.
5316 EFB PAR 16 Not used for Comm
setup.
This parameter indicates the count of
MS/TP tokens passed to this drive.
Code Description
EFB Protocol Reference
Modbus BACnet