188 ACQ550-U1 User’s Manual
Embedded fieldbus
Relay output control
Using the fieldbus for relay output control requires:
Drive parameter values set as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. More than 3 relays requires the addition of a relay extension module.
For example: To control relays 1 and 2 using serial communication:
Set parameters 1401
RELAY OUTPUT 1 and 1402 RELAY OUTPUT 1 = 35 (COMM).
Note: Relay status feedback occurs without configuration as defined below.
Drive Parameter Value Setting
Protocol Reference
Modbus
BACnet
ABB DRV
DCU
PROFILE
1401 RELAY
OUTPUT 1
35
(COMM)
Relay Output 1
controlled by fieldbus.
40134 bit 0 or 00033 BO0
1402 RELAY
OUTPUT 2
35
(COMM)
Relay Output 2
controlled by fieldbus.
40134 bit 1 or 00034 BO1
1403
RELAY
OUTPUT 3
35
(COMM)
Relay Output 3
controlled by fieldbus.
40134 bit 2 or 00035 BO2
1410
1
RELAY
OUTPUT 4
35
(COMM)
Relay Output 4
controlled by fieldbus.
40134 bit 3 or 00036 BO3
1411
1
RELAY
OUTPUT 5
35
(COMM)
Relay Output 5
controlled by fieldbus.
40134 bit 4 or 00037 BO4
1412
1
RELAY
OUTPUT 6
35
(COMM)
Relay Output 6
controlled by fieldbus.
40134 bit 5 or 00038 BO5
Drive
Parameter
Value Setting
Protocol Reference
Modbus
BACnet
ABB DRV DCU PROFILE
0122 RO 1-3
STATUS
Relay 1…3
status.
40122 0122 BI0…
BI2
0123
RO 4-6
STATUS
Relay 4…6
status.
40123 0123 BI3…
BI5