200 ACQ550-U1 User’s Manual
Embedded fieldbus
The ACQ550 supports the following Modbus function codes for coils:
1xxxx Mapping – Modbus discrete inputs. The drive maps the following
information to the 1xxxx Modbus set called Modbus Discrete Inputs:
bit-wise map of the
STATUS WORD (selected using parameter 5305 EFB CTRL
PROFILE). The first 32 inputs are reserved for this purpose.
discrete hardware inputs, numbered sequentially beginning with input 33.
The following table summarizes the 1xxxx reference set:
Function code Description
01 Read coil status
05 Force single coil
15 (0x0F Hex) Force multiple coils
Modbus
ref.
Internal location
(all profiles)
ABB DRV
(5305 = 0 OR 2)
DCU PROFILE
(5305 = 1)
10001
STATUS WORD – Bit 0 RDY_ON READY
10002 STATUS WORD Bit 1 RDY_RUN ENABLED
10003
STATUS WORD – Bit 2 RDY_REF STARTED
10004 STATUS WORD Bit 3 TRIPPED RUNNING
10005 STATUS WORD Bit 4 OFF_2_STA
1
ZERO_SPEED
10006
STATUS WORD – Bit 5 OFF_3_STA
1
ACCELERATE
10007 STATUS WORD – Bit 6 SWC_ON_INHIB DECELERATE
10008 STATUS WORD – Bit 7 ALARM AT_SETPOINT
10009
STATUS WORD – Bit 8 AT_SETPOINT LIMIT
10010 STATUS WORD – Bit 9 REMOTE SUPERVISION
10011 STATUS WORD – Bit 10 ABOVE_LIMIT REV_REF
10012
STATUS WORD – Bit 11 EXT2 REV_ACT
10013 STATUS WORD Bit 12 RUN_ENABLE PANEL_LOCAL
10014 STATUS WORD – Bit 13 N/A FIELDBUS_LOCAL
10015
STATUS WORD – Bit 14 N/A EXT2_ACT
10016
STATUS WORD – Bit 15 N/A FAULT
10017 STATUS WORD – Bit 16 Reserved ALARM
10018
STATUS WORD – Bit 17 Reserved REQ_MAINT
10019 STATUS WORD Bit 18 Reserved DIRLOCK
10020
STATUS WORD – Bit 19 Reserved LOCALLOCK
10021
STATUS WORD – Bit 20 Reserved CTL_MODE
10022 STATUS WORD Bit 21 Reserved Reserved
10023
STATUS WORD – Bit 22 Reserved Reserved
10024
STATUS WORD – Bit 23 Reserved Reserved
10025
STATUS WORD – Bit 24 Reserved Reserved
10026 STATUS WORD Bit 25 Reserved Reserved
10027
STATUS WORD – Bit 26 Reserved REQ_CTL