ACQ550-U1 User’s Manual 223
Embedded fieldbus
Note: For Present Value Access Types, R = Read-only, W = Writeable,
C = Commandable. Commandable values support priority arrays & relinquish
defaults.
BACnet quick-start sequence
The following steps summarize the process for enabling and configuring BACnet on
the ACQ550:
1. Enable BACnet protocol: Set drive parameter 9802,
COMM PROTOCOL SEL = BACNET
(5).
Note: If you cannot see the desired selection on the panel, your drive does not have
that protocol software in the application memory.
To confirm this selection, read drive parameter 5301,
EFB PROTOCOL ID. It should
read x5xx (where “x” is any value).
2. Place the BACnet channel in “reset”: Set drive parameter 5302,
EFB STATION ID = 0.
This setting holds the BACnet communication channel in reset while remaining
settings are completed.
3. Define the MS/TP baud rate.
Set drive parameter 5303,
EFB BAUD RATE = appropriate value.
4. Define the Device Object Instance ID.
To define a specific device object instance value, use drive parameters 5311 and
5317 (object instance values must be unique and in the range 1 to 4,194,303).
To use the drive’s MS/TP MAC ID as the device object instance value, set drive
parameter 5311 and 5317 = 0.
BACnet requires a unique Device Object ID for each device on the BACnet
network.
5. Define a unique MS/TP MAC ID. Set drive parameter 5302,
EFB STATION ID =
appropriate value.
Once this parameter is set to a non-zero value, current BACnet settings are
“latched” and used for communication until the channel is reset.
AV26 MBOX DATA This object holds the mailbox function’s
parameter value – a value that was read,
or is to be written. See BV15 and BV16.
None W
AV27 EXT PID STPT This object sets the External PID
controller setpoint. The corresponding
drive parameter is 4211. Control requires
parameter 4210,
PID SETPOINT SEL, value
= 19 (
INTERNAL).
Percent C
Instance
ID
Object Name Description Units
Present Value
Access Type