242 ACQ550-U1 User’s Manual
Fieldbus adapter
4 OFF_2_STA 1 OFF2 inactive
0 OFF2 ACTIVE
5 OFF_3_STA 1 OFF3 inactive
0 OFF3 ACTIVE
6SWC_ON_INHIB1SWITCH-ON INHIBIT ACTIVE
0 SWITCH-ON INHIBIT NOT ACTIVE
7 ALARM 1 Alarm (See section Alarm listing on page 258 for details
on alarms.)
0 No alarm
8AT_SETPOINT 1
OPERATING. Actual value equals (within tolerance limits)
the reference value.
0 Actual value is outside tolerance limits (not equal to
reference value).
9 REMOTE 1 Drive control location:
REMOTE (EXT1 or EXT2)
0 Drive control location: LOCAL
10 ABOVE_LIMIT 1 Supervised parameter’s value > supervision high limit.
Bit remains “1” until supervised parameter’s value <
supervision low limit.
See Group 32: SUPERVISION.
0 Supervised parameter’s value < supervision low limit.
Bit remains “0” until supervised parameter’s value >
supervision high limit.
See Group 32: SUPERVISION.
11 EXT CTRL LOC 1 External control location 2 (
EXT2) selected
0 External control location 1 (EXT1) selected
12 EXT RUN ENABLE 1 External Run Enable signal received
0 No External Run Enable signal received
13… 15 Unused
ABB Drives profile (FBA)
STATUS WORD
Bit Name Value
Description
(Correspond to states/boxes in the state diagram)