ACQ550-U1 User’s Manual 253
Diagnostics
3 DEV OVERTEMP Drive heatsink is overheated. Temperature is at or above limit.
R1…R4: 115 °C (239 °F)
R5, R6: 125 °C (257 °F)
Check for and correct:
Fan failure.
Obstructions in the air flow.
Dirt or dust coating on the heat sink.
Excessive ambient temperature.
Excessive motor load.
4
SHORT CIRC Fault current. Check for and correct:
A short-circuit in the motor cable(s) or motor.
Supply disturbances.
5
RESERVED Not used.
6 DC UNDERVOLT Intermediate circuit DC voltage is not sufficient. Check for and correct:
Missing phase in the input power supply.
Blown fuse.
Undervoltage on mains.
7
AI1 LOSS Analog input 1 loss. Analog input value is less than AI1 FAULT LIMIT (3021).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI1 FAULT LIMIT (3021) and 3001 AI<MIN FUNCTION.
8 AI2 LOSS Analog input 2 loss. Analog input value is less than AI2 FAULT LIMIT (3022).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI2 FAULT LIMIT (3022) and 3001 AI<MIN FUNCTION.
9 MOT OVERTEMP Motor is too hot, based on either the drive’s estimate or on temperature
feedback.
Check for overloaded motor.
Adjust the parameters used for the estimate (3005…3009).
Check the temperature sensors and Group 35: MOTOR TEMP MEAS
parameters.
10
PANEL LOSS Panel communication is lost and either:
Drive is in local control mode (the control panel displays LOC or OFF), or
Drive is in remote control mode (AUTO) and is parameterized to accept
start/stop, direction or reference from the control panel.
To correct check:
Communication lines and connections.
Parameter 3002
PANEL COMM ERR.
Parameters in Group 10: START/STOP/DIR and Group 11:
REFERENCE SELECT (if drive operation is AUTO).
11
ID RUN FAIL The Motor ID Run was not completed successfully. Check for and correct:
Motor connections.
Motor parameters 9905…9909.