ACQ550-U1 User’s Manual 257
Diagnostics
Fault resetting
The ACQ550 can be configured to automatically reset certain faults. Refer to
parameter Group 31: AUTOMATIC RESET.
WARNING! If an external source for start command is selected and it is active, the
ACQ550 may start immediately after fault reset.
Flashing red LED
To reset the drive for faults indicated by a flashing red LED:
• Turn the power off for 5 minutes.
Red LED
To reset the drive for faults indicated by a red LED (on, not flashing), correct the
problem and do one of the following:
• Press RESET from the control panel.
• Turn the power off for 5 minutes.
Depending on the value of 1604
FAULT RESET SEL, the following could also be used to
reset the drive:
• digital input
• serial communication.
When the fault has been corrected, the motor can be started.
History
For reference, the last three fault codes are stored into parameters 0401, 0412,
0413. For the most recent fault (identified by parameter 0401), the drive stores
additional data (in parameters 0402…0411) to aid in troubleshooting a problem. For
example, parameter 0404 stores the motor speed at the time of the fault.
1014 PAR PFC IO 3 IO configuration is not complete – the drive is unable to allocate a digital
input (interlock) for each PFC motor (parameters 8120
INTERLOCKS and
8127
MOTORS).
1015 RESERVED Not used.
1016 PAR USER LOAD C Parameter values for the user load curve are inconsistent. Check that the
following conditions are met:
• 3704
LOAD FREQ 1 < 3707 LOAD FREQ 2 < 3710 LOAD FREQ 3 <
3713
LOAD FREQ 4 < 3716 LOAD FREQ 5.
• 3705 LOAD TORQ LOW 1 < 3706 LOAD TORQ HIGH 1.
• 3708
LOAD TORQ LOW 2 < 3709 LOAD TORQ HIGH 2.
• 3711
LOAD TORQ LOW 3 < 3712 LOAD TORQ HIGH 3.
• 3714 LOAD TORQ LOW 4 < 3715 LOAD TORQ HIGH 4.
• 3717
LOAD TORQ LOW 5 < 3718 LOAD TORQ HIGH 5.
Fault
code
Fault name in
panel
Description and recommended corrective action