ACQ550-U1 User’s Manual 259
Diagnostics
2007 AI2 LOSS Analog input 2 is lost, or value is less than the minimum setting.
Check:
Input source and connections.
Parameter that sets the minimum (3022).
Parameter that sets the alarm/fault operation (3001).
2008
PANEL LOSS Panel communication is lost and either:
Drive is in local control mode (the control panel displays LOC), or
Drive is in remote control mode (AUTO) and is parameterized to
accept start/stop, direction or reference from the control panel.
To correct check:
Communication lines and connections.
Parameter 3002
PANEL COMM ERR.
Parameters in Group 10: START/STOP/DIR and Group 11:
REFERENCE SELECT (if drive operation is REM).
2009
DEVICE
OVERTEMP
Drive heatsink is hot. This alarm warns that a DEVICE OVERTEMP fault
may be near.
R1…R4: 100 °C (212 °F)
R5, R6: 110 °C (230 °F)
Check for and correct:
Fan failure.
Obstructions in the air flow.
Dirt or dust coating on the heat sink.
Excessive ambient temperature.
Excessive motor load.
2010
MOTOR TEMP Motor is hot, based on either the drive’s estimate or on temperature
feedback. This alarm warns that a
MOT OVERTEMP fault trip may be
near. Check:
Check for overloaded motor.
Adjust the parameters used for the estimate (3005…3009).
Check the temperature sensors and Group 35: MOTOR TEMP
MEAS.
2011
RESERVED Not used.
2012
MOTOR STALL Motor is operating in the stall region. This alarm warns that a MOTOR
STALL fault trip may be near.
2013
(Note 1)
AUTORESET This alarm warns that the drive is about to perform an automatic fault
reset, which may start the motor.
To control automatic reset, use Group 31: AUTOMATIC RESET.
2014
(Note 1)
AUTOCHANGE This alarm warns that the PFC autochange function is active.
To control PFC, use Group 81: PFC CONTROL and the PFC macro
on page 64.
2015
PFC I LOCK This alarm warns that the PFC interlocks are active, which means that
the drive cannot start the following:
Any motor (when Autochange is used).
The speed regulated motor (when Autochange is not used).
2016/
2017
RESERVED Not used.
Alarm
code
Display Description