ACQ550-U1 User’s Manual 273
Technical data
Fuses, 500…600 V drives
Emergency stop devices
The overall design of the installation must include emergency stop devices and any
other safety equipment that may be needed. Pressing STOP on the drive’s control
panel does NOT:
• generate an emergency stop of the motor
• separate the drive from dangerous potential.
-125A-4 125 160 150 JJS-150
-157A-4 157 200
160 JJS-200
-180A-4 180 250
200 JJS-250
-246A-4 246 250
250 JJS-250
00467918.xls C
ACQ550-U1-
see below
Input current
A
Input power (mains) fuses
IEC 60269 gG (A)
UL Class T (A) Bussmann type
-02A7-6 2.7 10
10 JJS-10
-03A9-6 3.9
-06A1-6 6.1
-09A0-6 9.0 16
15 JJS-15
-011A-6 11
-017A-6 17 25
25 JJS-25
-022A-6 22
-027A-6 27 35
40 JJS-40
-032A-6 32
-041A-6 41 50
50 JJS-50
-052A-6 52 60
60 JJS-60
-062A-6 62 80
80 JJS-80
-077A-6 77
100 JJS-100
-099A-6 99 125
150 JJS-150
-125A-6 125 160
175 JJS-175
-144A-6 144 200
200 JJS-200
00467918.xls C
ACQ550-x1-
see below
Input current
A
Input power (mains) fuses
IEC 60269 gG (A)
UL Class T (A) Bussmann type