292 ACQ550-U1 User’s Manual
Technical data
Air flow, 500…600 V drives
The following table lists heat loss and air flow data for 500…600 V drives.
-038A-4 R3 562 1919 134 79
-045A-4 R3 667
2278 280 165
-059A-4 R4 907
3098 280 165
-072A-4 R4 1120
3825 280 165
-078A-4 R4 1295 4423 280 165
-097A-4 R4 1440
4918 250 147
-125A-4 R5 1940 6625 404 238
-157A-4 R6 2310 7889 404 238
-180A-4 R6 2810
9597 404 238
-246A-4 R6 3260 11134 540 318
00467918.xls C
Drive Heat loss Air flow
ACQ550-U1- Frame size W BTU/hr m
3
/h ft
3
/min
-02A7-6 R2 46 157 88 52
-03A9-6 R2 68
232 88 52
-06A1-6 R2 124 423 88 52
-09A0-6 R2 170 581 88 52
-011A-6 R2 232
792 88 52
-017A-6 R2 337 1150 88 52
-022A-6 R3 457 1560 134 79
-027A-6 R3 562
1918 134 79
-032A-6 R4 667 2276 280 165
-041A-6 R4 907
3096 280 165
-052A-6 R4 1120
6820 280 165
-062A-6 R4 1295 4420 280 165
-077A-6 R6 1504 5136 404 238
-099A-6 R6 1821
6219 404 238
-125A-6 R6 2442
8339 404 238
-144A-6 R6 2813 9607 404 238
00467918.xls C
Drive Heat loss Air flow
ACQ550-x1- Frame size W BTU/hr m
3
/h ft
3
/min