ACQ550-U1 User’s Manual 41
Start-up, control with I/O and ID Run
ID RUN WITH THE ACQ CONTROL PANEL
Change parameter 9910
ID RUN to 1 (ON). Save the new setting
by pressing .
If you want to monitor actual values during the ID Run, go to
the Output mode by pressing repeatedly until you get
there.
Press to start the ID Run. The panel keeps switching
between the display that was shown when you started the ID
Run and the alarm display presented on the right.
In general, it is recommended not to press any control panel
keys during the ID Run. However, you can stop the ID Run at
any time by pressing .
After the ID Run is completed, the alarm display is not shown
any more.
If the ID Run fails, the fault display presented on the right is
shown.
SAVE
9910 ID RUN
PAR EDIT
ON
CANCEL SAVE
00:00
[1]
LOC
EXIT
0 A
0 Hz
0 % 0.
0.
0.
50.0Hz
LOC
DIR
MENU
00:00
00:00
ID run
ALARM
LOC
ALARM 2019
00:00
ID RUN FAIL
FAULT
LOC
FAULT 11