ACQ550-U1 User’s Manual 47
Control panel
Start-Up Assistant Mode
To start the Start-Up Assistant, follow these steps:
The Start-up Assistant will guide you through the start-up.
The Start-up Assistant guides you through the basic programming of a new drive.
(You should familiarize yourself with the control panel operation and follow the steps
outlined above.) At the first start, the drive automatically suggests entering the first
task, Language Select. The assistant also checks the values entered to prevent
entries that are out of range.
The Start-up Assistant is divided into tasks. You may activate the tasks one after the
other, as the Start-up Assistant suggests, or independently.
Note: If you want to set the parameters independently, use the Parameters Mode.
The table below lists the tasks of the assistants and the relevant drive parameters.
Depending on the selection made in the Application task (parameter 9902 APPLIC
MACRO), the Start-up Assistant decides which consequent tasks it suggests.
1
Select MENU to enter the main menu
2
Select ASSISTANTS with the UP/DOWN
buttons and select ENTER.
3
Scroll to START-UP ASSISTANT with the
UP/DOWN buttons and select SEL.
Select to answer
Do you want to use the START-UP
ASSISTANT? YES or NO
4
Change the values suggested by the
assistant to your preferences and then
press SAVE after every change.
Name Description
Language select Selecting the language
Motor set-up Setting the motor data
Performing the motor identification. (If the speed limits are not in the allowed
range: Setting the limits.)
Application Selecting the application macro
PID control Selecting the source for the process reference
(If AI1 is used: Setting analog input AI1 limits, scale, inversion)
Setting the reference limits
Setting the speed (reference) limits
Setting the source and limits for the process actual value