82 ACQ550-U1 User’s Manual
Parameters
6433 AL2RANGE90TO 0.0…100.0% 0.1% -
Group 81: PFC CONTROL
8103 REFERENCE STEP 1 0.0…100.0% 0.1% 0.0%
8104
REFERENCE STEP 2 0.0…100.0% 0.1% 0.0%
8105
REFERENCE STEP 3 0.0…100.0% 0.1% 0.0%
8109 START FREQ 1 0.0…500.0 Hz 0.1 Hz -U1: 60.0 Hz
8110
START FREQ 2 0.0…500.0 Hz 0.1 Hz -U1: 60.0 Hz
8111 START FREQ 3 0.0…500.0 Hz 0.1 Hz -U1: 60.0 Hz
8112
LOW FREQ 1 0.0…500.0 Hz 0.1 Hz -U1: 30.0 Hz
8113
LOW FREQ 2 0.0…500.0 Hz 0.1 Hz -U1: 30.0 Hz
8114 LOW FREQ 3 0.0…500.0 Hz 0.1 Hz -U1: 30.0 Hz
8115
AUX MOT START D 0.0…3600.0 s 0.1 s 5.0 s
8116
AUX MOT STOP D 0.0…3600.0 s 0.1 s 3.0 s
8117
NR OF AUX MOT 0…4 1 1
8118
AUTOCHNG INTERV -0.1 = TEST MODE, 0.0 = NOT SEL,
0.1…336.0 h
0.1h 0.0h (NOT SEL)
8119
AUTOCHNG LEVEL 0.0…100.0% 0.1% 50.0%
8120
INTERLOCKS 0…6 1 4 (DI4)
8121 REG BYPASS CTRL 0=NO, 1 = YES 10 (NO)
8122
PFC START DELAY 0.00…10.00 s 0.01 s 0.50 s
8123
PFC ENABLE 0=NOT SEL, 1 = ACTIVE 10 (NOT SEL)
8124 ACC IN AUX STOP 0.0 = NOT SEL, 0.1…1800.0 s 0.1 s 0.0 s (NOT SEL)
8125
DEC IN AUX START 0.0 = NOT SEL, 0.1…1800.0 s 0.1 s 0.0 s (NOT SEL)
8126
TMED AUTOCHNG 0…4 1 0 (NOT SEL)
8127 MOTORS 1…7 1 2
8128
AUX START ORDER 1=EVEN RUNTIME, 2 = RELAY ORDER 11 (EVEN RUNTIME)
Group 98: OPTIONS
9802 COMM PROT SEL 0=NOT SEL, 1 = STD MODBUS,
4=
EXT FBA, 5 = BACNET
10 (NOT SEL)
Code Name Range Resolution Default User S

Table of Contents