Fuses (IEC)
aR fuses by Cooper Bussmann for protection against short-circuit in the input power cable
of drive are listed below.
Ultrarapid (aR) fuses
FuseInput
current
(A)
Drive type
ACQ580-34-
SizeType DIN 43653VA
2
sA
U
n
= 400 V, IEC
2170M540869074000400212246A-4
2170M5410690145000500257293A-4
3170M6410690210000630321365A-4
3170M6411690300000700401442A-4
3170M6412690465000800401505A-4
3170M64146909450001000505585A-4
3170M64146909450001000569650A-4
U
n
= 480 V, IEC
1170M441069042000315209246A-4
2170M540869074000400233293A-4
2170M5410690145000500307365A-4
3170M6410690210000630363442A-4
3170M6411690300000700363505A-4
3170M6411690300000700389585A-4
3170M6412690465000800441650A-4
3AXD00000586715
Note:
• See also sections:
•
Protecting the drive and the input power cable in short-circuits (page 87)
•
Protecting the drive against thermal overload (page 87)
•
Protecting the input power cable against thermal overload (page 88).
• In multicable installations, install only one fuse per phase (not one fuse per conductor).
• Fuses with higher current rating than the recommended ones must not be used. Fuses
with lower current rating can be used.
• Fuses from other manufacturers can be used if they agree with the ratings and the melting
curve of the fuse does not exceed the melting curve of the fuse mentioned in the table.