Start-up
Setting the parameters
1. Power up the drive.
2. If no warning is shown,
make sure that the value of both parameters 15.01 Extension module type and 15.02
Detected extension module is CHDI-01.
If warning A7AB Extension I/O configuration failure is shown,
make sure that the value of parameter 15.02 is CHDI-01.
set parameter 15.01 value to CHDI-01.
You can now see the parameters of the extension module in parameter group 15 I/O
extension module.
3. Set the parameters of the extension module to applicable values.
Parameter setting example for relay output
This example shows how make relay output RO4 of the extension module indicate the
reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Reverse15.07 RO4 source
1 s15.08 RO4 ON delay
1 s15.09 RO4 OFF delay
Fault and warning messages
Warning A7AB Extension I/O configuration failure.
Technical data
Into an option slot on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Reley outputs (50…52, 53…55)
1.5 mm
2
Maximum wire size
12 V / 10 mAMinimum contact rating
250 V AC / 30 V DC / 2 AMaximum contact rating
1500 VAMaximum breaking capa-
city
115/230 V inputs (70…78)
1.5 mm
2
Maximum wire size
115 to 230 V AC ±10%Input voltage
2 mAMaximum current leakage
in digital off state
Isolation areas
212 CHDI-01 115/230 V digital input extension module