Layout example, door open (standard drive module
configuration)
PE
T3/W2
T2/V2
T1/U2
1
4
5
6
7
9
3
2a
2a
13
14
10
11
3
2d
2e
2e
L1/U1
L2/V1
L3/W1
2b
2c
14
12
A
A
AA
15
B– B
16
B
B
8
Motor cable including the protective ground con-
ductor of the drive module
9Supporting frame of the cabinet1
Drive module control unit.10
Vertical (2a, 2b) and horizontal (2c, 2d) air baffles
that separate the cool and hot areas (leak-proof
lead-throughs). See section Preventing the recir-
culation of hot air (page 55).
2
Note: The upper door air inlet is critical for proper
cooling of the control unit.
External control cables11
Optional air baffle that is needed when there is
no fan on the lower part of the cabinet door. See
section Preventing the recirculation of hot
air (page 55).
2e
Grounding screws12Cabinet grounding busbar (PE)3
Alternative to grounding screws (12)13Input power cable including the protective ground
conductor (PE) of the drive
4
Air flow to the roof14Disconnector and fuses5
Air flow through the drive module15Contactor6
Air flow through the LCL filter16Drive module7
--LCL filter module8
Note: The power cable shields can also be grounded to the drive module grounding terminals.
Guidelines for planning the mechanical installation 53