18 EN - Quick installation and start-up guide
Terminal sizes
• Frame sizes R0…R8: 0.14…1.5 mm
2
(all terminals)
• Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)…20 mA, R
in
< 500 ohm] or voltage [ 0(2)…10 V, R
in
> 200 kohm]
input as selected with parameter 12.15 AI1 unit selection.
2)
Current [0(4)…20 mA, R
in
= 100 ohm] or voltage [ 0(2)…10 V, R
in
> 200 kohm]
input as selected with parameter 12.25 AI2 unit selection.
3)
Total load capacity of the auxiliary voltage output +24V (X2:10) =
6.0 W (250 mA / 24 V) - User can use this source for either of the I/O connections
(DI1... DI2- RO1 or DI3...DI6 - RO2~RO3).
4)
Connected with jumpers at the factory.
5)
Applicable for R0~R2 frames only.
6)
Use shielded twisted-pair cables for digital signals.
7)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
8)
Input signal
9)
Output signal
For information on cable connection and drive operation, see Control Connections in
the hardware manual (3AXD50000170661).
Install optional modules, if any
See chapter Electrical installation in ACQ80-04 hardware manual.
ACQ80R0-R8 QIG.book Page 18 Friday, February 1, 2019 1:18 PM