EasyManuals Logo

ABB ACQ80-04 Quick Installation And Start-Up Guide

ABB ACQ80-04
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
18 EN - Quick installation and start-up guide
EN
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
Terminal sizes
Frame sizes R0…R8: 0.14…1.5 mm
2
(all terminals)
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
Notes
1)
Current [0(4)…20 mA, R
in
< 500 ohm] or voltage [ 0(2)…10 V, R
in
> 200 kohm]
input as selected with parameter 12.15 AI1 unit selection.
2)
Current [0(4)…20 mA, R
in
= 100 ohm] or voltage [ 0(2)…10 V, R
in
> 200 kohm]
input as selected with parameter 12.25 AI2 unit selection.
3)
Total load capacity of the auxiliary voltage output +24V (X2:10) =
6.0 W (250 mA / 24 V) - User can use this source for either of the I/O connections
(DI1... DI2- RO1 or DI3...DI6 - RO2~RO3).
4)
Connected with jumpers at the factory.
5)
Applicable for R0~R2 frames only.
6)
Use shielded twisted-pair cables for digital signals.
7)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
8)
Input signal
9)
Output signal
For information on cable connection and drive operation, see Control Connections in
the hardware manual (3AXD50000170661).
Install optional modules, if any
See chapter Electrical installation in ACQ80-04 hardware manual.
ACQ80R0-R8 QIG.book Page 18 Friday, February 1, 2019 1:18 PM