EasyManua.ls Logo

ABB ACQ80-04 - Check the Insulation of the Input and Motor Cables and the Motor

ABB ACQ80-04
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 EN - Quick installation and start-up guide
EN
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
Check the insulation of the input and motor cables and the
motor
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
Check the insulation of the motor cable and motor before connecting it to the
drive.
Measure the insulation resistance between each phase conductor and the
Protective Earth conductor using a measuring voltage of 1000 V DC. The
insulation resistance of an ABB motor must exceed 100 Mohm (reference value at
25 °C or 77 °F). For the insulation resistance of other motors, see the
manufacturer’s instructions.
Note: Moisture inside the motor casing will reduce the insulation resistance. If
moisture is suspected, dry the motor and repeat the measurement.
ohm
M
3~
U1
V1
W1
PE
ACQ80R0-R8 QIG.book Page 8 Friday, February 1, 2019 1:18 PM

Other manuals for ABB ACQ80-04

Related product manuals