Technical data 57
DC fuses
Typical AC input power cable specifications
Note: For DC power cable specifications are based on the PV manufacturer
Drive type
ACQ80-04-
Fuse (A) Drive type
ACQ80-04-
Fuse (A)
3-phase U
N
= 380…480 V
0kW75-4 10 022kW-4 100
01kW1-4 10 030kW-4 125
01kW5-4 10 037kW-4 160
02kW2-4 10 045kW-4 160
03kW0-4 16 055kW-4 200
04kW0-4 20 075kW-4 315
05kW5-4 25 090kW-4 315
07kW5-4 32 110kW-4 400
011kW-4 50 132kW-4 450
015kW-4 63 160kW-4 550
18kW5-4 80
Drive type
ACQ80-04
IEC
Copper wire cable
mm
2
Aluminum wire cable
mm
2
0kW75-4 3 x 1.5 + 1.5 -
01kW1-4 3 x 1.5 + 1.5 -
01kW5-4 3 x 1.5 + 1.5 -
02kW2-4 3 x 1.5 + 1.5 -
03kW0-4 3 x 1.5 + 1.5 -
04kW0-4 3 x 2.5 + 2.5 -
05kW5-4 3 x 2.5 + 2.5 -
07kW5-4 3 x 2.5 + 2.5 -
011kW-4 3 x 6.0 + 6.0 -
015kW-4 3 x 10 + 10 -
18kW5-4 3 x 10 + 10 -
022kW-4 3 x 16 + 16 -
030kW-4 3 x 25 + 16 3 x 35
037kW-4 3 x 35 + 16 3 x 50
045kW-4 3 x 35 + 16 3 x 70
055kW-4 3 x 50 + 25 3 x 70
075kW-4 3 x 95 + 50 -
090kW-4 3 x 120 + 70 -
110kW-4 3 x 150 + 70 -
132kW-4 2 x (3 x 70 + 35) -
160kW-4 2 x (3 x 95 + 50) -
ACQ80R0-R8 QIG.book Page 57 Friday, February 1, 2019 1:18 PM