56 Technical data
gR fuses
Drive type
ACQ80-04
Minimum
short
circuit
current
1)
Input
current
gG (IEC 60269)
Rated
current
I
N
I
2
t Rated
voltage
ABB
designation
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 380…480 V
0kW75-4 48 4.2 25 125 690 170M2694 00
01kW1-4 48 5.3 25 125 690 170M2694 00
01kW5-4 80 6.4 32 275 690 170M2695 00
02kW2-4 80 9.0 32 275 690 170M2695 00
03kW0-4 128 11.5 40 490 690 170M2696 00
04kW0-4 128 15.0 40 490 690 170M2696 00
05kW5-4 200 20.2 50 1000 690 170M2697 00
07kW5-4 256 27.2 63 1800 690 170M2698 00
011kW-4 400 40.0 80 3600 690 170M2699 00
015kW-4 170 33.0 63 1450 690 170M1565 000
18kW5-4 170 39.0 63 1450 690 170M1565 000
022kW-4 280 45.0 80 2550 690 170M1566 000
030kW-4 380 62 100 4650 690 170M1567 000
037kW-4 480 73 125 8500 690 170M1568 000
045kW-4 480 88 160 16000 690 170M1569 000
055kW-4 700 106 200 15000 690 170M3815 1
075kW-4 1000 145 250 28500 690 170M3816 1
090kW-4 1280 169 315 46500 690 170M3817 1
110kW-4 1520 206 350 68500 690 170M3818 1
132kW-4 2050 246 450 105000 690 170M5809 2
160kW-4 2200 293 500 145000 690 170M5810 2
1)
minimum short-circuit current of the device