Parameters List 39
EN
TR
ZH
32.49 Supervision 5 low -21474836.00… 21474836.00 - 0.00
32.50 Supervision 5 high -21474836.00… 21474836.00 - 0.00
32.51 Supervision 5 hysteresis 0.00...100000.00 - 0.00
32.55 Supervision 6 function See parameter 32.05
Supervision 1 function
- Disabled[0]
32.56 Supervision 6 action No action[0], Warning[1],
Fault[2], Fault if running[3]
- No action[0]
32.57 Supervision 6 signal See parameter 32.07
Supervision 1 signal
- Zero[0]
32.58 Supervision 6 filter time 0.000...30.000 s 0.000
32.59 Supervision 6 low -21474836.00… 21474836.00 - 0.00
32.60 Supervision 6 high -21474836.00… 21474836.00 - 0.00
32.61 Supervision 6 hysteresis 0.00...100000.00 - 0.00
35 Motor thermal protection
35.01 Motor estimated temperature -60…1000 °C °C 0
35.02 Measured temperature 1 -60…5000 °C °C 0
35.03 Measured temperature 2 -60…5000 °C °C, 0
35.05 Motor overload level 0.0...300.0 % % 0.0
35.11 Temperature 1 source
0, 1, 5...7, 11 -
Estimated
temperature
[1]
35.12 Temperature 1 fault limit
-60…5000 °C °C
130 °C or 266
°F
35.13 Temperature 1 warning limit -60…5000 °C °C 110 °C
35.14 Temperature 1 AI source
0...2 -
Not
selected[0]
35.21 Temperature 2 source See parameter 35.11
Temperature 1 source
- Disabled[0]
35.22 Temperature 2 fault limit -60…5000 °C °C 130 °C
35.23 Temperature 2 warning limit -60…5000 °C °C 110 °C
35.24 Temperature 2 AI source See parameter 35.14
Temperature 1 AI source
-
Not
selected[0]
35.50 Motor ambient temperature -60…100 °C °C 20
35.51 Motor load curve 50…150 % 100
35.52 Zero speed load 50…150 % 100
35.53 Break point 1.00 500.00 Hz 45.00
35.54 Motor nominal temperature rise 0…300 °C °C 80
35.55 Motor thermal time constant 100…10000 s 256
35.56 Motor overload action No action[0],Warning only[1],
Warning and fault[2]
-
Warning and
fault[2
35.57 Motor overload class Class 5[0], Class 10[1], Class
20[2], Class 30,[3] Class 40[4]
- Class 20[2]
Index Name Range/List Unit Default
Disabled[0] 2 × Pt100 analog I/O[6]
Estimated temperature[1] 3 × Pt100 analog I/O[7]
1 × Pt100 analog I/O[5] Direct temperature[11]
Not selected[0] AI1 actual value[1] AI2 actual value[2] Other...
ACQ80R0-R8 QIG.book Page 39 Friday, February 1, 2019 1:18 PM