Parameters List 47
EN
TR
ZH
79.15 Enable tank level operation Disable[0]
79.17 Tank low sensor DI5[6]
79.18 Tank high sensor See parameter 79.17 Tank
low sensor.
DI6[7]
79.31 Pump start time
2)
00:00:00...23:59:59 - 00:00:00
79.32 Pump stop time
2)
00:00:00...23:59:59 - 00:00:00
79.40 MPPT reference 0...6 Enable[1]
79.41 Start DC voltage 225...800 V 225
79.42 PV cell min voltage 225...800 V 225
79.43 PV cell max voltage 225...800 V 800
79.51 Pump minimum speed 0...3000 rpm 500
79.52 Pump maximum speed 0...3000 rpm 3000
79.56 Boost voltage 225...600 V 450
79.57 Boost factor 0.75...1.50 - 1.00
79.61 Fault reset time 1.0...1200.0 s 120.0
79.71 Motor factor Not applicable.
80 Flow calculation
80.01 Calculated flow 0.00...200000.00 m
3
/h 0.00
80.03 Total flow 0.00...21474836.00 m
3
0.00
80.06 Today’s flow 0.00...21474836.00 m
3
0.00
80.07 Sensored flow 0...2147483648 - 0
80.13 Flow function PQ curve[101], DI based[115] - PQ curve[101]
80.14 Flow calc gain 0.50...2.00 - 1.00
80.21 Pump nominal speed 0...30000 rpm 0
80.26 Calc low speed 0.00...32767.00 Hz 5.00
80.29 Reset flow
Not selected[0], Reset[1] -
Not
selected[0]
80.50 PQ curve P1 0.00...32767.00 kW 0.00
80.51 PQ curve P2 0.00...32767.00 kW 0.00
80.52 PQ curve P3 0.00...32767.00 kW 0.00
80.53 PQ curve P4 0.00...32767.00 kW 0.00
80.54 PQ curve P5 0.00...32767.00 kW 0.00
80.60 Q value Q1 0.00...200000.00 m
3
/h 0.00
80.61 Q value Q2 0.00...200000.00 m
3
/h 0.00
80.62 Q value Q3 0.00...200000.00 m
3
/h 0.00
80.63 Q value Q4 0.00...200000.00 m
3
/h 0.00
80.64 Q value Q5 0.00...200000.00 m
3
/h 0.00
82 Pump protections
82.02 Dry run source
0...8 -
Min load
current[8]
Index Name Range/List Unit Default
Disable[0] DI1[2] DI3[4] DI5[6] Other...
Enable[1] DI2[3] DI4[5] DI6[7]
Not selected[0] DI1[2] DI3[4] DI5[6] Other...
Selected[1] DI2[3] DI4[5] DI6[7]
Disable[0] DI1[2] DI3[4] DI5[6] Other...
Enable[1] DI2[3] DI4[5] DI6[7]
ACQ80R0-R8 QIG.book Page 47 Friday, February 1, 2019 1:18 PM