46 Parameters List
58.101
Data I/O 1
0...6, 11...16, 21, 24, 31, 32,
33, 40, 41, Other...
- CW 16bit[1]
58.102 Data I/O 2 See parameter 58.101 - Ref1 16bit[2]
58.103 Data I/O 3 See parameter 58.101 - Ref2 16bit[3]
58.104 Data I/O 4 See parameter 58.101 - SW 16bit[4]
58.105 Data I/O 5 See parameter 58.101 - Act1 16bit[5]
58.106 Data I/O 6 See parameter 58.101 - Ac;t2 16bit[6]
58.107 Data I/O 7 See parameter 58.101 - None[0]
...
58.114 Data I/O 14 See parameter 58.101 - None[0]
79 Start stop control
1)
Works only with assistant control panel.
2)
Timed function must be enabled to use this feature. See parameter
79.10
Operating mode
.
79.01 Solar status word1 0b0000...0b1111 0b0000
79.02 Solar status word2 0b0000...0b1111 0b0000
79.10 Operating mode
0...5 -
Manual In 1
Start; stop[4]
79.11 Manual input source 1 0...7 - DI1[2]
79.12 Manual input source 2 See parameter 79.11 Manual
input source 1.
- DI2[3]
Index Name Range/List Unit Default
None[0] SW 16bit[4] Ref1 32bit[12] Act2 32bit[16] AO1 data storage[32]
CW 16bit[1] Act1 16bit[5] Ref2 32bit[13] CW2 16bit[21] AO2 data storage[34]
Ref1 16bit[2] Act2 16bit[6] SW 32bit[14] SW2 16bit[24]
Feedback data
storage[40]
Ref2 16bit[3] CW 32bit[11] Act1 32bit[15] RO/DIO control word[31]
Setpoint data
storage[41]
Bit Name Bit Name Bit Name
0 Ready ON 5 DC over volt 10 Motor phase loss
1 Ready run 6 DC under volt 11 Supply phase loss
2 Running 7 Minimum speed 12 Motor stall
3 Fault 8 Short circuit 13 Over current
4 Dry run 9 Earth fault 14 Ext fault1
15 Start delay active
Bit Name Bit Name Bit Name
0 Ext fault2 4 Device Overtemp 9 Start enable
1 AI1 supervision 5 ID run failed 10 Run enable
2 Reserved 6 Output wiring 11 Tank filling on
3 Panel loss 7 Safe torque off 12 Cloud detected
8 Motor overtemp 13...15 Reserved
Auto[0] Manual In1P Start; In2 Stop[2] Fieldbus A[4]
Manual In 1 Start; stop[1] Timed function[3]
1)
Embedded fieldbus[5]
Not selected[0] DI1[2] DI3[4] DI5[6] Other...
Selected[1] DI2[3] DI4[5] DI6[7]
ACQ80R0-R8 QIG.book Page 46 Friday, February 1, 2019 1:18 PM