Technical data 55
gG fuses
Drive type
ACQ80-04
Minimum
short
circuit
current
1)
Input
current
gG (IEC 60269)
Rated
current
I
N
I
2
t Rated
voltage
ABB
designation
type
IEC 60269
size
A A A A
2
s V
3 phases U
N
= 400 V (380...480 V)
0kW75-4 48 4.2 6 110 500 OFAF000H6 000
01kW1-4 48 5.3 6 110 500 OFAF000H6 000
01kW5-4 80 6.4 10 360 500 OFAF000H10 000
02kW2-4 80 9.0 10 360 500 OFAF000H10 000
03kW0-4 128 11.5 16 740 500 OFAF000H16 000
04kW0-4 128 15.0 16 740 500 OFAF000H16 000
05kW5-4 200 20.2 25 2500 500 OFAF000H25 000
07kW5-4 256 27.2 32 4500 500 OFAF000H32 000
011kW-4 320 40.0 50 15500 500 OFAF000H50 000
015kW-4 320 33.0 40 7700 500 OFAF000H40 000
18kW5-4 400 39.0 50 16000 500 OFAF000H50 000
022kW-4 500 45.0 63 20100 500 OFAF000H63 000
030kW-4 800 62.0 80 37500 500 OFAF000H80 000
037kW-4 1000 73.0 100 65000 500 OFAF000H100 000
045kW-4 1000 88.0 100 65000 500 OFAF000H100 000
055kW-4 1300 106.0 125 103000 500 OFAF000H125 00
075kW-4 1700 145.0 160 185000 500 OFAF000H160 00
090kW-4 3300 169.0 250 600000 500 OFAF000H250 0
110kW-4 5500 206.0 315 710000 500 OFAF000H315 1
132kW-4 6400 246.0 355 920000 500 OFAF000H355 1
160kW-4 7800 293.0 425 1300000 500 OFAF000H425 2