Parameters List 33
EN
TR
ZH
10.25 RO1 ON delay 0.0...3000.0 s 0
10.26 RO1 OFF delay 0.0...3000.0 s 0
10.27 RO2 source See parameter 10.24 RO1
source
- Running [7]
10.28 RO2 ON delay 0.0...3000.0 s 0
10.29 RO2 OFF delay 0.0...3000.0 s 0
10.30 RO3 source See parameter 10.24 RO1
source
- Fault (-1) [15]
10.31 RO3 ON delay 0.0...3000.0 s 0
10.32 RO3 OFF delay 0.0...3000.0 s 0
10.99 RO/DIO control word 0b0000...0b1111 - 0b0000
10.101 RO1 toggle counter 0...4294967000 - -
10.102 RO2 toggle counter 0...4294967000 - -
10.103 RO2 toggle counter 0...4294967000 - -
11 Standard DIO, FI, FO
11.05 DIO1 configuration Digital output[0], Input[],
Frequency output [2]
- Input[1]
11.21 DI5 configuration Digital input[0], Frequency
input [1]
- Digital input[0]
11.38 Freq in 1 actual value 0…16000 Hz -
11.39 Freq in 1 scaled value -32768.000...32767.000 - -
11.42 Freq in 1 Min 0…16000 Hz 0
11.43 Freq in 1 Max 0…16000 Hz 16000
11.44 Freq in 1 at scaled Min -32768.000...32767.000 - 0.000
11.45 Freq in 1 at scaled Max -32768.000...32767.000 - 50.00
12 Standard AI
12.02 AI fo rce s ele ction 0b000... 0b1111 - 0b0000
12.03 AI supervision function 0...4 - No action[0]
12.04 AI supe rvision se lection 0b 000...0b1111 - 0b0000
12.11 AI1 actual value 0.000…10.000 V 10.000
12.12 AI1 scaled value -32768.000...32767.000 - 50.000
12.13 AI1 forced value 0.000…10.000 V 0
12.15 AI1 unit selection V[2], mA[10] - V[2]
12.16 AI1 filter time 0.000…30.000 s 0.100
12.17 AI1 Min 0.000…10.000 V 0.000
12.18 AI1 Max 0.000…10.000 V 10.000
12.19 AI1 scaled at AI1 Min -32768.000...32767.000 - 0.000
Index Name Range/List Unit Default
Bit Name Bit Name Bit Name Bit Name
0 RO1 1 RO2 2 RO3 3...15 Reserved
Bit Name Bit Name Bit Name
0 AI1 1 AI2 2…15 Reserved
No action[0] Warning [2]
Speed ref safe[4] - Not
applicable.
Fault[1]
Last speed[3]
Bit Name Bit Name Bit Name
0 AI1 < MIN 2 AI2 < MIN 4...15 Reserved
1 AI1 > MAX 3 AI2 > MAX
ACQ80R0-R8 QIG.book Page 33 Friday, February 1, 2019 1:18 PM