Note: The UL Listing of drive and MMP combinations applies only to drives that are
mounted in appropriately sized metal enclosures that are capable of containing any
drive component failure. Wall-mounted drives with UL Type 1 kits (optional) are not
covered by the UL combination listing of drives with MMPs.
WARNING!
Use fuses for the short-circuit protection of a wall-mounted drive with the UL Type
1 kit (optional). Serious injury, fire, or damage to equipment can result from the
use of MMPs instead of fuses.
Minimum enclosure volume
4)
MMP type
1) 2) 3)
Frame
Type ACS380-
04xx-…
in
3
dm
3
1-phase U
N
= 230 V
185030.3
MS132-6.3 & S1-M3-25
5)
R002A4-1
185030.3
MS132-10 & S1-M3-25
5)
R003A7-1
185030.3MS165-16R104A8-1
185030.3MS165-16R106A9-1
185030.3MS165-20R107A8-1
185030.3MS165-25R209A8-1
185030.3MS165-32R212A2-1
3-phase U
N
= 230 V
185030.3
MS132-6.3 & S1-M3-25
5)
R102A4-2
185030.3
MS132-10 & S1-M3-25
5)
R103A7-2
185030.3
MS132-10 & S1-M3-25
5)
R104A8-2
185030.3MS165-16R106A9-2
185030.3MS165-16R107A8-2
185030.3MS165-16R109A8-2
185030.3MS165-20R212A2-2
185030.3MS165-32R317A5-2
185030.3MS165-42R325A0-2
457775.0MS165-54R4032A-2
457775.0MS5100-100 / MS165-80R4048A-2
457775.0MS5100-100 / MS165-80R4055A-2
3-phase U
N
= 480 V
185030.3
MS132-4.0 & S1-M3-25
5)
R001A8-4
185030.3
MS132-6.3 & S1-M3-25
5)
R102A6-4
185030.3
MS132-6.3 & S1-M3-25
5)
R103A3-4
185030.3
MS132-10 & S1-M3-25
5)
R104A0-4
185030.3
MS132-10 & S1-M3-25
5)
R105A6-4
142 Technical data