Free space requirements
Free space requirementFrame
Sides
2)
Below
Above
1)
inmminmminmm
00375375All
1)
Drives with the optional UL Type 1 kit: 50 mm (2 in), measured from the top of the hood.
2)
A side-mounted option module requires 20 mm (0.8 in) of free space on the right side of the drive.
Losses, cooling data and noise
Drives with frame size R0 have natural convection cooling. Drives with frame size
R1…R4 have a cooling fan. The air flow direction is from bottom to top.
Frame
size
NoiseAir flow
Typical power loss
1)
Type
ACS380-
04xx-…
dB(A)CFMm
3
/hBTU/hW
1-phase U
N
= 230 V
R0< 30--1133302A4-1
R0< 30--1674903A7-1
R16333572296704A8-1
R16333573179306A9-1
R163335736210607A8-1
R25937633149209A8-1
R259376339211512A2-1
3-phase U
N
= 230 V
R16333571333902A4-2
R16333571945703A7-2
R16333572467204A8-2
R163335737911106A9-2
R163335735810507A8-2
R163335747814009A8-2
R259376350814912A2-2
R3667512890426517A5-2
R36675128135839825A0-2
R469881501194350032A-2
R469881501914561048A-2
R469881502307676055A-2
3-phase U
N
= 400/480 V
R0<30--962801A8-4
R16333571504402A6-4
R16333571885503A3-4
Technical data 145