EMC filter typeType
ACS380-
04xx-…
Schaffner order codeABB order code
FN 3258-100-35RFI-34055A-2
3-phase U
N
= 400 V
FN 3258-16-44RFI-3201A8-4
FN 3258-16-44RFI-3202A6-4
FN 3258-16-44RFI-3203A3-4
FN 3258-16-44RFI-3204A0-4
FN 3258-16-44RFI-3205A6-4
FN 3258-16-44RFI-3207A2-4
FN 3258-16-44RFI-3209A4-4
FN 3258-30-33RFI-3312A6-4
FN 3258-30-33RFI-3317A0-4
FN 3258-30-33RFI-3325A0-4
FN 3258-100-35RFI-34032A-4
FN 3258-100-35RFI-34038A-4
FN 3258-100-35RFI-34045A-4
FN 3258-100-35RFI-34050A-4
If you use an external EMC filter, you must disconnect the internal EMC filter. Refer to
the electrical installation instructions.
Electrical power network specification
Input voltage range:
ACS380-04xx-xxxx-1 drives: 1-phase 200 … 240 V AC -15% … +10%
Voltage (U1)
ACS380-04xx-xxxx-2 drives: 3-phase 200 … 240 V AC -15% … +10%
ACS380-04xx-xxxx-4 drives: 3-phase 380 … 480 V AC -15% … +10%
Public low voltage networks. Symmetrically grounded TN-S system, IT
(ungrounded), corner-grounded delta. Consult ABB before connecting
to other systems (for example, TT, or midpoint grounded delta).
Network type
65 kA when protected by fuses given in the fuse tables.Rated conditional
short-circuit current
(IEC 61800-5-1)
US and Canada: The drive is suitable for use on a circuit capable of de-
livering not more than 100 kA symmetrical amperes (rms) at 480 V
maximum when protected by fuses given in the fuse table.
Short-circuit current
protection (UL 61800-
5-1, CSA C22.2
No. 274-13)
Technical data 151