Mechanical installation
Contents of this chapter
This chapter tells how to examine the installation site, unpack and examine the delivery
and install the drive mechanically.
Installation alternatives
You can install the drive:
with screws on to a wall
with screws on to an assembly plate
on to a DIN installation rail (IEC/EN 60715, top hat type, width 35 mm [1.4 in] ×
height 7.5 mm [0.3 in]).
Installation requirements:
The drive is designed for cabinet installation and has a degree of protection of IP20
/ UL open type as standard. A UL Type 1 kit is available as an option.
Make sure that there is a minimum of 75 mm (3 in) of free space at the top and
bottom of the drive (at the cooling air inlet and outlet), measured from the frame.
With the optional UL Type 1 kit, make sure that there is a minimum of 50 mm (2 in)
of free space at the top (measured from the top of the hood) and 75 mm (3 in) at
the bottom of the drive.
You can install several drives side by side. Note that side-mounted options require
20 mm (0.8 in) of space on the right side of the drive.
Install R0 drives vertically, because they do not have a cooling fan.