■ Connection procedure
WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur. If you are not a qualified electrical
professional, do not do installation or maintenance work.
Refer to Terminal data for the power cables (page 147) for the tightening torques.
1.
Do the steps in section Electrical safety precautions (page 17) before you start the
work.
2. Remove the screw on the drive front cover, then remove the front cover.
3. Attach the residual voltage warning sticker in the local language to the drive.
4. Strip the motor cable.
5. Ground the motor cable shield under the grounding clamp for 360-degree grounding.
6. Twist the motor cable shield into a bundle, mark it with yellow-green insulation tape,
install a cable lug, and connect it to the grounding terminal.
7. Connect the phase conductors of the motor cable to terminals T1/U, T2/V and T3/W.
Electrical installation – IEC 73