ABB ACS380 - Alternate Power Cable Types

ABB ACS380
238 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Use as motor cablingUse as input power cablingCable type
YesYes
PE
Symmetrical shielded (or ar-
mored) cable with three phase
conductors and symmetrically
constructed PE conductor and
a shield (or armor)
YesYes
PE
Symmetrical shielded (or ar-
mored) cable with three phase
conductors and a shield (or ar-
mor), and separate PE conduct-
or/cable
1)
1)
A separate PE conductor is required if the conductivity of the shield (or armor) is not sufficient for the PE use.
Alternate power cable types
Use as motor cablingUse as input power cablingCable type
Yes with phase conductor
smaller than 10 mm
2
(8 AWG)
Cu, or motors up to 30 kW
(40 hp).
Yes with phase conductor
smaller than 10 mm
2
(8 AWG)
Cu.
PVC
Four-conductor cabling in PVC
conduit or jacket (three phase
conductors and PE)
Note: Shielded or armored
cable, or cabling in metal con-
duit is always recommended to
minimize radio frequency inter-
ference.
Yes with phase conductor
smaller than 10 mm
2
(8 AWG)
Cu, or motors up to 30 kW
(40 hp)
Yes
EMT
Four-conductor cabling in met-
al conduit (three phase con-
ductors and PE), eg, EMT, or
four-conductor armored cable
Guidelines for planning the electrical installation 53