2 Update notice
ADDED:
Changing internal overtemperature supervision from DI6 to another digital input
By default, digital input DI6 is used for the internal overtemperature supervision of the
drive cabinet. If it is required to use DI6 for an other purpose, change the overtemperature
supervision wiring from DI6 to another free digital input either on the control unit or on the
CMOD-01 multifunction extension module. Active the overtemperature supervision in the
new digital input with these parameter settings:
1. Select the correct digital input from parameter 31.01 External event 1 source.
2. Check that parameter 31.02 External event 1 type is set to Fault = 0.
For more information, see the firmware manual.
WARNING! Always connect the internal overtemperature supervision of the drive
cabinet to a free digital input or CMOD-01 multifunction extension module if
disconnected from digital input DI6. Activate the change. Disconnection of
overtemperature supervision leads to overtemperature and can damage the drive.
PNP configuration for digital inputs (DIGITAL IN)
CHANGED:
Note! By default, digital input DI6 is used for the internal overtemperature supervision of
the cabinet. If it needs to be changed, see section
Changing internal overtemperature supervision
from DI6 to another digital input on page 2.
X504:10
X504:18
+24 V DC
0VDC
PNP connection (source)
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
X504:18
X504:10
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
PNP connection (source)
Internal +24 V power supply External +24 V power supply