94 Start-up
In an edit view:
Use and to move the cursor left and right.
Use and to change the value.
•Press (Save) to accept the new setting, or press
(Cancel) to go back to the previous view without
making changes.
To give the drive a name that will be shown at the top,
press .
If you do not want to change the default name (ACS580),
continue straight to the set-up of the motor nominal
values by pressing (Next).
For information on editing text, see ACS580 firmware
manual 3AXD50000016097 [English]).
Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly
as shown on the motor nameplate.
Example of a nameplate of an induction (asynchronous) motor
:
Check that the motor data is correct. Values are
predefined on the basis of the drive size but you should
verify that they correspond to the motor.
Start with the motor nominal current.
Motor nominal cos Φ and nominal torque are optional.
Press (Next) to continue.
This step is optional, and requires rotating the motor. Do
not do this if it could cause any risk, or if the mechanical
set-up does not allow it.
To do the direction test, select Spin the motor and press
(Next).
Press the Start key on the panel to start the drive.
M2AA 200 MLA 4
1475
1475
1470
1470
1475
1770
32.5
56
34
59
54
59
0.83
0.83
0.83
0.83
0.83
0.83
3GAA 202 001 - ADA
180
IEC 34-1
6210/C36312/C3
Cat. no
35
30
30
30
30
30
50
50
50
50
50
60
690 Y
400 D
660 Y
380 D
415 D
440 D
V
Hz kW
r/min A
cos
IA/IN
t
E/s
Ins.cl. F
IP 55
No
IEC 200 M/L 55
3
motor
ABB Motors