Parameters 119
06.18 Start inhibit status
word
Start inhibit status word. This word specifies the source of
the inhibiting signal that is preventing the drive from
starting.
The conditions marked with an asterisk (*) only require that
the start command is cycled. In all other instances, the
inhibiting condition must be removed first.
See also parameter 06.16 Drive status word 1, bit 1.
This parameter is read-only.
-
0000h…FFFFh Start inhibit status word. 1 = 1
No. Name/Value Description Def/
FbEq16
Bit Name Description
0 Not ready run 1 = DC voltage is missing or drive has not been
parametrized correctly. Check the parameters in groups
95 and 99.
1 Ctrl location
changed
* 1 = Control location has changed
2 SSW inhibit 1 = Control program is keeping itself in inhibited state
3 Fault reset * 1 = A fault has been reset
4 Lost start enable 1 = Start enable signal missing
5 Lost run enable 1 = Run enable signal missing
6 FSO inhibit 1 = Operation prevented by FSO-xx safety functions
module
7 STO 1 = Safe torque off active
8 Current calibration
ended
* 1 = Current calibration routine has finished
9 ID run ended * 1 = Motor identification run has finished
10 Auto phase ended * 1 = Autophasing routine has finished
11 Em Off1 1 = Emergency stop signal (mode off1)
12 Em Off2 1 = Emergency stop signal (mode off2)
13 Em Off3 1 = Emergency stop signal (mode off3)
14 Auto reset inhibit 1 = The autoreset function is inhibiting operation
15 Jogging active 1 = The jogging enable signal is inhibiting operation