250 Parameters
0…300% Maximum deviation from expected deceleration rate. 1 = 1%
31.38 Ramp stop
supervision delay
If parameter 31.37 Ramp stop supervision is set to 0%,
this parameter defines the maximum time a ramp stop is
allowed to take. If the motor has not stopped when the
time elapses, the drive trips on 73B1 Stop failed, sets bit
14 of 06.17 Drive status word 2, and coasts to a stop.
If 31.37 is set to a value other than 0%, this parameter
defines a delay between the receipt of the stop command
and the activation of the supervision. It is recommended to
specify a short delay to allow the speed change rate to
stabilize.
0 s
0…32767 s Maximum ramp-down time, or supervision activation delay. 1 = 1 s
31.40 Disable warnings Selects warnings to be suppressed. The parameter is a
16-bit word with each bit corresponding to a warning.
Whenever a bit is set to 1, the corresponding warning is
suppressed.
The bits of this binary number correspond to the following
warnings:
0000b
000b...1101b Warning suppression word. 1 = 1
31.42 Overcurrent fault limit Sets a custom motor current fault limit.
The drive automatically sets an internal motor current limit
according to the drive hardware. The internal limit is
appropriate in most cases, but this parameter can be used
to set a lower current limit, for example, to protect a
permanent magnet motor from demagnetization.
With this parameter at 0.0 A, only the internal limit is in
force.
0.00...30000.0 A Custom motor current fault limit -
No. Name/Value Description Def/
FbEq16
Bit Fault
0 Overvoltage
1 Reserved
2 Encoder 1
3 Encoder 2
4…15 Reserved