Parameters 343
96.03 Access levels active Shows which access levels have been activated by pass
codes entered into parameter 96.02 Pass code.
This parameter is read-only.
0001h
0000h…FFFFh Active access levels. -
96.04 Macro select Selects the application macro. For more information, see
ACS880 primary control program firmware manual
(3AUA0000085967[English]).
After a selection is made, the parameter reverts
automatically to Done.
Done
Done Macro selection complete; normal operation. 0
Factory Factory macro 1
Hand/Auto Hand/Auto macro 2
Sequence control Sequential control macro 5
FIELDBUS Reserved. 6
96.05 Macro active Shows which application macro is currently selected. For
more information, see ACS880 primary control program
firmware manual (3AUA0000085967[English]).
To change the macro, use parameter 96.04 Macro select.
Factory
Factory Factory macro 1
Hand/Auto Hand/Auto macro 2
Sequence control Sequential control macro 5
FIELDBUS Fieldbus control macro 6
96.06 Parameter restore Restores the original settings of the control program, ie.
parameter default values.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Restoring is completed. 0
No. Name/Value Description Def/
FbEq16
Bit Name
0 End user
1 Service
2 Advanced programmer
3…10 Reserved
11 OEM access level 1
12 OEM access level 2
13 OEM access level 3
14 Parameter lock
15 Reserved