Fault tracing 433
80A0 AI supervision
Programmable fault:
12.03 AI supervision
function
An analog signal is outside
the limits specified for the
analog input.
Check signal level at the analog
input.
Check the wiring connected to the
input.
Check the minimum and maximum
limits of the input in parameter
group 12 Standard AI.
Check the auxiliary code.
80B0 Signal supervision
(Editable message text)
Programmable fault:
32.06 Supervision 1 action
Fault generated by a signal
supervision function.
Check the source of the fault
(parameter 32.07, 32.17 or 32.28).
80B1 Signal supervision 2
(Editable message text)
Programmable fault:
32.16 Supervision 2 action
Fault generated by the signal
supervision 2 function.
Check the source of the fault
(parameter 32.17 Supervision 2
signal).
80B2 Signal supervision 3
(Editable message text)
Programmable fault:
32.26 Supervision 3 action
Fault generated by the signal
supervision 3 function.
Check the source of the fault
(parameter 32.27 Supervision 3
signal).
9081 External fault 1
(Editable message text)
Programmable fault: 31.01
External event 1 source
31.02 External event 1 type
Fault in external device 1. Check the external device.
Check setting of parameter 31.01
External event 1 source.
9082 External fault 2
(Editable message text)
Programmable fault: 31.03
External event 2 source
31.04 External event 2 type
Fault in external device 2. Check the external device.
Check setting of parameter 31.03
External event 2 source.
9083 External fault 3
(Editable message text)
Programmable fault: 31.05
External event 3 source
31.06 External event 3 type
Fault in external device 3. Check the external device.
Check setting of parameter 31.05
External event 3 source.
9084 External fault 4
(Editable message text)
Programmable fault: 31.07
External event 4 source
31.08 External event 4 type
Fault in external device 4. Check the external device.
Check setting of parameter 31.07
External event 4 source.
9085 External fault 5
(Editable message text)
Programmable fault: 31.09
External event 5 source
31.10 External event 5 type
Fault in external device 5. Check the external device.
Check setting of parameter 31.09
External event 5 source.
FA81 Safe torque off 1 loss Safe torque off function is
active, ie. STO circuit 1 is
broken.
Check safety circuit connections.
For more information, see
appropriate drive hardware manual
and description of parameter 31.22
STO indication run/stop (page
245).
Check the auxiliary code, The code
contains location information,
especially with parallel-connected
inverter modules
FA82 Safe torque off 2 loss Safe torque off function is
active, ie. STO circuit 2 is
broken.
Code
(hex)
Fault Cause What to do