Set the Device ID in the BACnet > Device page, and optionally set a Device Name:
Note: Device ID is the BACnet device instance number. Every BACnet controller within the site must receive a
unique BACnet instance number to ensure proper communications. This BACnet instance number
should be unique even across subnets. By default, it is set is set to the entire numeric portion of the
Controller's serial number.
If the CBXi device is to act as a BBMD (allowing BACnet communication between Ethernet subnets), enter
the relevant parameters on the BBMD/NAT page: (see
BACnet IP Broadcast Management Device (BBMD)
on page 16 for more detail)