Plug-in Bullet Style Circuit Breakers
for Groups 16 or 17
Comcode
Size
(A)
Breaker
Positions
Wire Ga
(min)
407998137 3 1 14
407998145
5 1 14
407998152
10 1 14
407998160
15 1 14
407998178
61 1 12
407998186
20 1 12
407998194
25 1 10
407998202
30 1 10
407998210
45 1 8
407998228
50 1 8
407998236
60 1 6
407998244
70 1 6
407998251
80* 1* 4
407998269
90* 1* 4
407998277
100* 1* 2
408185353
125** 2** 2
408185346
150** 2** 1/0
408564941
200 *** 3 *** 2/0
408535752
250 *** 3 *** 4/0
*
Breakers larger than 70A require that an adjacent position on either side to be left unpopulated for heat dissipation purposes if loaded at >80% capacity.
**
125A and 150A double-pole breakers require an adapter bus kit, per 848631479, jumper two positions together prior to lug termination.
***
200A and 250A three-pole breakers require an adapter bus kit, 848745662, jumper three positions together prior to lug termination.
Figure 8-8: ED83143-31 Group 16 14-position (H469-434/4827/4830 G97, 97A) and Group
17 22-position (H469-434/4827/4830 G98, 98A) 600A DC Distribution Panels
Single position circuit breaker (Plug - in, 3-100A)
Also accepts dual position plug - in - breakers (125-150A)
and three-position plug in breakers (200-250A)***