Lugs and Hardware
Lug
Comcode
Type
Std Wire Ga
(Class B)
Flex Wire Ga
(Class I)
Metric
Wire Size
(mm
2
)
Hardware Kit
(Grade 2)
For 1-position breakers or fuses (single-hole load, double-hole and return lugs)
405356171 load 14-10 14-10 6 provided
405356171 rtn 14-10 14-10 6 848201919
405348178 load 8 8 10 provided
405348178 rtn 8 8 10 848201919
406338400 load 6 6 16 provided
406338400 rtn 6 6 16 848201919
405347576 load 4 4 25 provided
405347576 rtn 4 4 25 848201919
405348202 load 2 -- 35 provided
405348202 rtn 2 -- 35 848201919
405347683 load -- 2 -- provided
405347683 rtn -- 2 -- 848201919
407817568 load 1/0 -- 50 provided
407817568 rtn 1/0 -- 50 848201919
407817550 load 2/0*** 1/0*** 70*** provided
407817550 rtn 2/0*** 1/0*** 70*** 848201919
407817576 load -- 2/0*** -- provided
407817576 rtn -- 2/0*** -- 848201919
***Only 5 return lugs of the indicated size will fit on the internal panel return bus.
Table 8-D: ED83143-31 Group 16 and Group 17 DC Distribution Panels, Lugs and Hardware Table