To DC Loads
847867132 Bolt Kit
Torque to 300 in-lbs (34 Nm)
5 Positions for Large
U.S. Circuit Breakers
Alarm Card
9” REF
(229mm)
Connects to
Charge Return Bus
9” REF
(229mm)
Terminal Card (See Note and CLR Card Assignment View)
Large Circuit Breaker Kits
for Groups 1, 4, 101, and 104
Comcode
Size
(A)
Breaker
Posi-
tions
Wire Ga
(min)
108908187 125 1 2
108908179 150 1 1/0
108908195 175 1 2/0
108908203 225 1 4/0
108908211 300 2 (2) 4/0*
108908237 400 2 (2) 4/0*
108908229 500 3 (3) 4/0*
108908252 600 3 (3) 4/0*
108984782 800 4 (4) 4/0*
*Cables must be the same length and terminate at a
common at each end.
Lugs and Hardware
Lug
Comcode
Type
Std Wire
Ga
(Class B)
Flex Wire
Ga
(Class I)
Metric
Wire Size
(mm
2
)
Hardware
Kit
(Grade 2)
For 1, 2, or 3-position breakers (double-hole load and return lugs)
406338665
load 2 -- 35
847867132
rtn 2 -- 35
405348228
load 1/0 -- 50
rtn 1/0 -- 50
405348236
load 2/0 1/0 70
rtn 2/0 1/0 70
406021725
load -- 2/0 --
rtn -- 2/0 --
405348251
load 4/0 -- --
rtn 4/0 -- --
405347923
load -- 4/0 120
rtn -- 4/0 120
Note
Jumper straps (J1 to J3) on the CLR card shall be left
in the factory default 5-12 position for use with ABB
Power Shunt RPM monitoring. Move these jumper
straps to the “Bypass” 1-8 position to permit shunt
monitoring with non-ABB equipment. Protection for
this wiring must be provided by the user when these
current-limiting resistors are bypassed.
Figure 8-4: ED83143-31 Group 5 (H469-434/4827/4830 G48/A, G110/A, G111/A, G112/A, or G113/A)
1000A (800A e/w LVLD) DC Distribution Panel
Distribution Panels (continued)
ED83143-31 Group 5