To DC Loads
Maximum Ampacity
200A per Column
400A Total
14 Positions for Clip-on
U.S. Circuit Breakers or
Alarm/Terminal Card
Clear
Covers
Torque to 35 in-lbs (4 Nm)
2-position Adapter Bus Bar per
848657912 (*part of lug kit in
Figure 8-3A)
Torque to 240 in-lbs (27 Nm)
6” REF
(152mm)
Clip-in Circuit Breakers
for Group 11
Comcode
Size
(A)
Breaker
Positions
Wire Ga
(min)
407098417 3 1 10
407098425
5 1 10
407098433
10 1 10
407098458
15 1 10
407098474
20 1 10
407098482
25 1 10
407098490
30 1 10
407245448
40 1 8
407098516
45 1 8
407098524
50 1 8
407098532
60 2 6
407098540
70 2 6
407098557
80 2 4
407098565
90 2 4
407098573
100 2 2
TPS Clip-in Fuses
for Group 11
Comcode
Size
(A)
Breaker
Positions
Wire Ga
(min)
CC408653406 holder 1 14
406700567 3 1 14
406700583
5 1 14
406700591
6 1 14
406700609
10 1 14
406700617
15 1 14
406700625
20 1 12
406700633
25 1 10
406700641
30 1 10
406700658
40 1 8
406700674
50 1 8
406700682
60 1 8
Figure 8-5: ED83143-31 Group 11 (H469-434/4827/4830 G11) 14-position 400A DC Distribution Panel
Distribution Panels (continued)
ED83143-31 Group 11