EasyManua.ls Logo

ABB NGC8200 - Page 86

ABB NGC8200
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86 | NGC8200 AND PGC1000 USER MANUAL | 2101510MNAH
To enable security:
1. Access the analyzer’s termination board.
2. Locate the security switch (S2).
3. Verify that the security switch (S2) is up (UNSECURE).
4. From PCCU entry mode, click the top node on the navigation tree. The Station Setup tab
displays.
5. Under the Security section, verify that Security Switch Status is OFF.
Figure 9-2: Security switch status: Off
6. Type a four-digit security code into Security Code Level 1. Level 1 access grants read only
access to the device.
7. Type a four-digit security code for Security Code Level 2. Level 2 access grants read and write
access to the device.
IMPORTANT NOTE: Record the security codes. They are not visible on the Station Setup tab after
you save them.
Figure 9-3: Configure security codes (example)
8. Click Send.
9. On the terminal board, flip the security switch (S2) down (Figure 9-4).

Table of Contents

Related product manuals