Mounting
Chapter 4
39
1SFC132003M0201
4:2.4 Minimum enclosure sizes
In applications where the softstarter is installed in an
enclosure, the following minimum enclosure sizes and fan
capacities are recommended.
(1mm = 0.0394 in)
Dimensions and drilling plan
See Chapter 3 “Description” .
4:2.5 Addings for marine applications
In order to be used in marine applications, the softstarter has
to be installed in a sheet steel enclosure. For the allowed
dimensions, see chapter 4:2.4.
For softstarters PST85...142 use the Marine kit
1SFA899004R1000.
Minimum enclosure
dimensions
Softstarter type W H D Fan capacity
PST30...72 300 400 250 42 m
3
/h
PST85...142 400 500 300 95 m
3
/h
PST175...300 500 600 300 210 m
3
/h
PSTB370...470 600 600 400 210 m
3
/h
PSTB570...1050 750 900 400 210 m
3
/h