Mounting
Chapter 4
38
1SFC132003M0201
4:2.2 Requirements
See Chapter 3 “Description” for environmental requirements.
4:2.3 Minimum distance to wall/front
To have a suitable cooling, the softstarter has to be mounted
vertically, and in such a way that the airways are not blocked,
see figure 2.
Follow the minimum distances to wall/front, figure 2 and the
table below.
The values are minimum distances.
(1mm = 0.0394 in)
Softstarter type A (mm) B (mm) C (mm)
PST30...72 100 10 20
PST85...300 100 10 20
PST175...300 100 10 20
PSTB370...470 150 15 20
PSTB570...1050 150 15 20
1SFC132044F0001
F
igure 2: Airways
A
B B
C
A
1SFC132045F0001
F
igure 2: Minimum distances, wall/front